TechnIcal SpecIfIcatIons
Inputs | |
---|---|
Analogue Inputs: | 4-20mA / 0-10V |
Sensor Inputs: | 2 Temperature-Humidity sensor |
Temperature | |
Range of Measurement: | -40…+120 C |
Degree of Accuracy: | +- 0.3 C |
Repeatability: | +-0.1 C |
HumIdIty | |
Range of Measurement: | 0-100 %rH |
Degree of Accuracy: | +- %2 %rH |
Repeatability: | +- %0.1 %rH |
Modbus: | 2 units RS485 Modbus RTU Only |
Relays: | 4 units 220 V 5A AC |
Logic Input: | 2 units |
Communication of GSM: | |
Quad-band: | 850/900/1800/1900MHz |
GPRS Multi-slot Class: | 12 |
GPRS Mobile Station :Class B | Class B |
Operation Temperature: | -40 °C to +85 °C |
Display: | 2×16 LCD Display |
Button: | 7 Control Button |
Memory: | 100.000 Recording / 10 Years memory storage life |
Power Supply : | 10-32V DC |
Power Consumption: | 4 W |
GSM Data Logger
FunctIonal SpecIfIcatIons
Our device 2 analogue data,2 temperature-humidity sensor data,2 logic input data and
16 modbus data parameter can read-record and send to web interface
• Read and send data to web time adjustable for all parameter
• Device can read and record 16 parameter with modbus protocol
• Device able to set 32 different alarms
• All alarms can set for all parameters as independently
• Relays are able to set for 32 alarms
• Device works on GSM
• Device able to send information SMS while in case of alarm
• All specifications can changeable by web and by SMS
• Data can be read by SMS immediately
• Device can change to another device specifications on web which device communicate by
modbus protocol
• On logic inputs,any other device can read position of logics• By logic information can send SMS and set alarms.
• There is an internal battery
• Device may sent data up to 24 hours from the moment of disconnection
• Can be controlled situation of battery,network and sending
• Real time works on device
• Time and date information can upgrade on web
• All data can reported which data sent to web and we can see all report on graphic-excel and PDF
• Device able to managed from web and all parameter can be change
• On 2 temperature-humidity sensor device able to work for indoor and outdoor in the same time
• All parameter adjustable by display and buttons.Menu are easy and so suitable
• Device can change the unit and parameter name which parameter device read as we wants
• All measurements adjustable on point and divide before shown on display
• Offset can be given for all parameters
• Temperature-Humidity sensor cable can be extended to 25 meters